GFEVF750 Series DC Power Fuse 750VDC 35‑800A aR

North‑American‑style aR DC power fuse GFEVF750 Series,750VDC 35‑800A,50kA breaking capacity. For battery pack,ESS & DC drives. CE RoHS compliant

GFEVF750-Series.-35-800A-750Vdc2

20+ Years Experience

Over 20 years in electrical protection and fuse manufacturing.

 

Strict Quality Control

Rigorous testing ensures reliable product performance.

 

GFEVF750‑Series North‑American‑Style DC Power Fuse,700/750VDC 35A‑800A Class aR

The GFEVF750 series is a DC fuse designed as a North-American-style aR power fuse for battery pack and ESS DC drives. This fuse supports 750VDC at 35-800A with 50kA breaking capacity.

,GFEVF750‑Series DC Power Fuse is high‑performance bolt‑on aR‑class fast‑acting fuse exclusively engineered for 700‑750Vdc DC‑system fault‑current protection. Rated for 750 Vdc with 35 A‑800 A current range and up to 50 kA rated breaking capacity (Time Constant:2.5±0.5 ms). This north‑american‑style cylindrical fuse delivers low arc‑voltage, low I²t energy let‑through and low watt‑loss, ideal for ESS energy‑storage, battery‑pack, DC‑drives and reduced‑voltage‑starter circuits. CE certified and RoHS‑compliant, designed to meet UL248.13 and IEC 60269.4 standards.

📄 Download Full Datasheet PDF  GFEVF750-Series.-35-800A-750Vdc2

Key Features & Benefits

  • ✅ Specially designed for pure DC‑application with excellent DC short‑circuit interrupting performance
  • ✅ Rated Breaking Capacity: 50 kA @750 Vdc (Time Constant 2.5±0.5 ms), operation class aR for semiconductor/battery DC‑protection
  • ✅ Low arc‑voltage & low energy let‑through (I²t), minimizing stress on protected power‑electronic components
  • ✅ Low watt‑loss, reducing continuous‑operation heating and overall system energy waste
  • ✅ Superior cycling capability, stable performance under repeated heavy‑load fluctuation
  • ✅ Can be applied in parallel configuration for higher total ampacity (follow official sizing guidelines)
  • ✅ Outstanding mechanical vibration & shock resistance, suitable for harsh industrial & mobile environments
  • ✅ Wide ambient‑temperature tolerance and strong anti‑current‑impingement capacity
  • ✅ CE approval, RoHS compliant; reference standards UL248.13 / IEC 60269‑4

Typical Applications

GFEVF750 series DC fuses are widely deployed for over‑current & short‑circuit protection for high‑voltage DC industrial and energy‑storage equipment:

  • 🔋 Electrical Energy‑Storage (ESS / Battery Energy‑Storage System)
  • 🔋 Industrial 750V battery pack over‑current & short‑circuit protection
  • ⚡ DC‑Drives motor system protection
  • ⚡ Reduced‑voltage starters equipment protection
  • ⚡ Power converters & rectifier equipment protection
  • ⚡ Backup protection for DC relay contacts

Main Electrical Ratings

Rated Voltage700Vdc / 750Vdc (max)
Rated Current Range35 A ~ 800 A
Rated Breaking Capacity50 kA @750 Vdc or lower
Time‑Constant Test Condition2.5 ± 0.5 ms
Operation ClassaR (semiconductor / DC fast‑acting protection)
Standards ReferenceUL248.13, IEC 60269‑4
CertificationsCE, RoHS Compliant

Part Number & Case Diameter Overview

Part Number rule: GFEVF750‑XXA‑YYR; XX‑rated current; YY‑case diameter(20R /26R /38R /51R)

  • 20 mm case(20R):35A‑60A
  • 26 mm case(26R):70A‑150A
  • 38 mm case(38R):125A‑400A
  • 51 mm case(51R):225A‑800A

Mechanical Dimensions

All dimension unit in mm. Tolerance refer to official datasheet drawing.

Case CodeCurrent RangeA±1.5B±1C±1D±1.5E±0.5F±0.5H±0.5G±0.5
20R35‑60A111.0020.0070.0090.508.5015.003.0013.0
26R70‑150A114.0026.0066.0090.008.5020.003.0012.0
38R125‑400A129.0038.0072.00100.5010.5025.006.0020.0
51R225‑800A129.0051.0072.00100.5010.5040.006.0020.0

Operating Conditions & Derating Rules

Temperature Condition

  • Normal operating ambient temperature:‑5 ℃ ~ +40 ℃
  • Allowable operating range:‑40 ℃ ~ +85 ℃
  • Storage temperature:‑40 ℃ ~120 ℃
  • Note: Recommended continuous working current ≤75% of fuse rated‑current. Above 40℃ ambient temperature requires current‑derating according to derating‑curve chart in datasheet.

Altitude Derating(Ka factor)

  • Standard condition: altitude ≤2000 m without derating.
  • Closed‑box installation above 2000 m: derate rated‑current 2‑5% per 1000 m elevation.
  • Open‑air installation: altitude thermal impact can generally be ignored.
  • Insulation gap correction should follow GB/T16935.1 for high‑altitude enclosed cabinet application.

Installation & Vibration Resistance

  • Supports vertical, horizontal or inclined mounting orientation.
  • High‑frequency vibration resistance ≥20g acceleration.
  • Forced air‑cooling can raise allowable operating‑current; refer to Kv cooling‑correction curve in datasheet.
  • Terminal contact resistance must remain low to avoid extra temperature‑rise.

Characteristic Curves Reference

  • Time‑Current Pre‑arcing curve (35‑200A /225‑800A)
  • Instantaneous peak let‑through cut‑off curve
  • Temperature derating coefficient curve
  • Altitude derating coefficient curve
  • Forced‑air cooling correction Kv curve

Full melting I²t, clearing I²t table and all graphic curves are included inside downloadable PDF datasheet.

FAQ — Technical & Commercial Questions

1: What does aR‑class stand for for GFEVF750 DC fuse?

A: aR is semiconductor‑protection class for high‑speed DC fuses, designed for fast short‑circuit fault‑clearing for high‑voltage battery and power‑electronic DC‑circuits, not general‑purpose gG cable‑protection fuse.

2: Is current derating required above 40℃ ambient temperature?

A: Yes. When ambient temperature higher than +40℃, derate fuse operating‑current follow the temperature‑derating graph inside datasheet. Recommended continuous load no higher than 75% nominal rating under normal environment.

3: Can multiple GFEVF750 fuses work in parallel for higher ampacity?

A: Yes, parallel‑installation is allowed to achieve higher total current capacity. You must strictly follow manufacturer sizing guidelines to guarantee balanced current‑sharing for parallel‑connected fuses.

4: Under what test condition is 50kA breaking‑capacity rated?

A: Breaking‑capacity rating 50kA@750Vdc is validated with DC‑circuit L/R time‑constant 2.5±0.5 ms.

5: Can I get engineering samples and full datasheet?

A: Yes, submit inquiry form to request engineering‑samples, datasheet PDF, dimension drawings or customized technical support.

Request Quotation / Technical Support

Please provide target part‑number, required quantity, real‑world application condition(voltage, working‑current, ambient‑temperature, altitude). Our application engineer will reply you within 24 working hours.

Related Products