GFHVT1500‑D‑105E 1500Vdc Fast‑Acting Fuse 400‑2000A
GFHVT1500‑D‑105E bolt‑on DC fuse,1500Vdc,400‑2000A,aR 250kA@L/R≤5ms. For BESS,wind‑power & DC‑drive protection. Download datasheet.
20+ Years Experience
Over 20 years in electrical protection and fuse manufacturing.
Strict Quality Control
Rigorous testing ensures reliable product performance.
Get a Quote
GFHVT1500‑D‑105E Series 1500Vdc Fast‑Acting Bolt‑Connected Square‑Body Fuse 400‑2000A
Product Overview
The GFHVT1500‑D‑105E series is heavy‑duty square‑body fast‑acting aR fuse link with D‑type four‑M10 bolt‑on busbar terminals, purpose‑built for high‑power DC circuits. Rated for 1500Vdc, current range 400A‑2000A, maximum interrupting capacity 250kA@1500Vdc (L/R ≤5ms), minimum breaking current>3In.
This high‑current bolt‑mount fuse features low arc‑voltage and low let‑through I²t, excellent cycling performance and ≥20g shock‑vibration resistance. Optimized for megawatt‑scale energy‑storage, wind‑power converter and heavy‑duty DC‑drive equipment. Tin‑plated terminal surface ensures stable bus‑bar contact.
Key Features & Benefits
- ✅ D‑type 4‑pcs M10 bolt‑on busbar connection, heavy‑duty for high‑current power loop
- ✅ Rated voltage 1500V DC, suitable for large‑scale DC energy‑storage architecture
- ✅ Fast‑acting aR semiconductor‑protection characteristic; low arc‑voltage & low let‑through I²t
- ✅ High interrupt rating: 250 kA @1500Vdc (L/R ≤5ms), minimum breaking current>3In
- ✅ Superior charge‑discharge cycling capability for frequent fluctuating DC working conditions
- ✅ Excellent mechanical shock & vibration resistance (≥20g), fits wind‑turbine & container‑ESS cabinet
- ✅ Tin‑plated contact surface for anti‑oxidation and stable electrical connection
- ✅ RoHS compliant, REACH statement available upon request
- ✅ Designed per UL 248‑13, IEC 60269‑4 standards
Main Electrical Specifications
| Parameter | Specification |
|---|---|
| Rated Voltage | 1500 Vdc |
| Rated Current Range | 400A‑2000A |
| Fuse Class | aR Fast‑acting |
| Max Interrupt Capacity | 250 kA @1500Vdc (L/R ≤5ms) |
| Minimum Breaking Current | >3×In |
| Terminal Type | D‑type bolt‑on, 4 pcs M10 mounting holes |
| Screw hole spec | Max hole depth12.5mm; Min thread length10mm |
| Plating | Tin(Sn) plate,3‑5 microns |
| Storage Temperature | -40 ℃ ~ +120 ℃ |
| Normal Operating Ambient | -5 ℃ ~ +40 ℃ |
| Allowable Operating Temperature | -40 ℃ ~ +85 ℃ |
Note: Recommended continuous operating current ≤75 % of fuse nominal rating under standard ambient‑temperature conditions. DC interrupt performance strongly depends on circuit L/R time‑constant.
Part Numbering Explanation
Example Model: GFHVT1500‑1000D‑105E
| Code | Definition |
|---|---|
| GF | Manufacturer Code (GFEV) |
| HV | High‑Speed / Fast‑Acting |
| T | Ceramics Body |
| 1500 | Rated Voltage:1500Vdc |
| 1000 | Rated Current(A) |
| D | Terminal: D‑type bolt‑on connection |
| 105E | Series Code |
Mechanical Dimensions & Installation
D‑type four‑M10 bolt‑on terminals, heavy‑duty for high‑current bus‑bar assembly, tin‑plated contact surface.
Installation note: M10 screw hole; max hole depth12.5 mm, minimum thread length10 mm. Apply proper tightening torque to avoid over‑heating contact points. Tin plating thickness:3‑5 microns.
Full Part List Table
| Part Number | Fuse Amps | Melting A²s | Clearing A²s | Power Loss 1.0In(W) | RoHS |
|---|---|---|---|---|---|
| GFHVT1500‑400D‑105E | 400A | 25834 | 136415 | 190 | ● |
| GFHVT1500‑500D‑105E | 500A | 57389 | 276828 | 195 | ● |
| GFHVT1500‑630D‑105E | 630A | 117654 | 567527 | 228 | ● |
| GFHVT1500‑700D‑105E | 700A | 162326 | 783014 | 245 | ● |
| GFHVT1500‑800D‑105E | 800A | 240110 | 1158220 | 255 | ● |
| GFHVT1500‑900D‑105E | 900A | 345759 | 1667836 | 276 | ● |
| GFHVT1500‑1000D‑105E | 1000A | 470616 | 2270110 | 290 | ● |
| GFHVT1500‑1100D‑105E | 1100A | 623250 | 3006366 | 310 | ● |
| GFHVT1500‑1200D‑105E | 1200A | 754483 | 3620561 | 319 | ● |
| GFHVT1500‑1250D‑105E | 1250A | 918230 | 4429260 | 326 | ● |
| GFHVT1500‑1300D‑105E | 1300A | 1009830 | 5254527 | 335 | ● |
| GFHVT1500‑1350D‑105E | 1350A | 1294848 | 6245949 | 347 | ● |
| GFHVT1400D‑105E | 1400A | 1399970 | 6986564 | 352 | ● |
| GFHVT1500‑1500D‑105E | 1500A | 1581795 | 7630093 | 360 | ● |
| GFHVT1500‑1600D‑105E | 1600A | 1927554 | 9297929 | 372 | ● |
| GFHVT1500‑1800D‑105E | 1800A | 2734600 | 13190870 | 392 | ● |
| GFHVT1500‑2000D‑105E | 2000A | 3603985 | 18860380 | 410 | ● |
Application Fields
- ⚡ Large‑scale & container‑type Battery‑Energy‑Storage System(BESS) main‑circuit short‑circuit protection
- ⚡ Wind‑power converter / wind turbine DC‑link short‑circuit protection
- ⚡ Heavy‑duty DC drives & industrial DC power equipment
- ⚡ Large‑capacity lithium‑ion battery‑cluster protection
- ⚡ DC bus‑bar over‑current & short‑circuit protection for high‑power energy‑storage station
Standards & Certifications
| Standard / Certificate | Status |
|---|---|
| UL 248‑13 | Design‑referenced |
| IEC 60269‑4 | Design‑referenced |
| RoHS | Compliant |
| REACH | Declaration available upon request |
Important: DC interrupt performance subject to actual circuit L/R time‑constant, confirm L/R ratio before project adoption.
Operating & Derating Conditions
Important: Recommended continuous operating current ≤75 % of fuse nominal rating under standard conditions.
Ambient Temperature Derating
Above 40 ℃ ambient temperature requires rated‑current derating according to derating curve. Below ‑5 ℃, pre‑arcing time for low overload will slightly extend.
Altitude Derating
Normal working altitude ≤2000 m. For closed‑enclosure applications at altitude 2000‑4500 m: derate rated current 2‑5 % per 1000 m elevation increase. Air insulation strength drops at high altitude, check clearance per GB/T 16935.1.
Forced Air Cooling Correction
Forced ventilation improves heat‑dissipation and raises allowable continuous operating current, refer to Kv correction curve vs wind‑speed(m/s).
Time‑Current Characteristic Curves
- Curve‑1 covers rating 400‑1200A
- Curve‑2 covers rating 1250‑2000A
- Curve tolerance: ±15 % on current axis. Minimum breaking current>3 × In.
Frequently Asked Questions
1: What is the interrupt rating and minimum breaking current for GFHVT1500‑D‑105E?
1: 250kA@1500Vdc for L/R ≤5ms; minimum breaking current>3In. DC interrupt performance is highly dependent on circuit L/R time‑constant.
2: What does D‑type terminal mean?
2: D‑type is four‑M10 bolt‑on bus‑bar connection for high‑current heavy‑duty application, tin‑plated contact surface for anti‑oxidation.
3: Can GFHVT1500‑D‑105E be used for wind‑turbine DC‑link protection?
3: Yes. This high‑current aR fuse is suitable for wind‑power converter DC‑link, large‑scale BESS and heavy‑duty DC‑drive. Need I²t coordination and L/R validation.
4: What derating shall I apply for sealed cabinet working at high altitude?
4: For sealed cabinets operating above 2000 m altitude, derate 2‑5 % per 1000 m elevation. Higher derating ratio applies for larger‑ampacity models.
5: What is suggested maximum continuous operating current?
5: Under standard ambient‑temperature conditions, continuous working current should not exceed 75 % of fuse nominal rated‑current.
Download Datasheet & Resources
📄 Download GFHVT1500‑D‑105E Series Datasheet(PDF) GFHVT1500-D-105E-Series.-400-2000A-1500Vdc-IR-250kA-4-Fast-Acting Fuse
📎 Request REACH Declaration | Request CAD Drawing | Ask Technical Support
Need fuse‑selection support? Contact our engineering team for I²t‑matching, L/R‑ratio evaluation and system‑coordination advice for your large‑power energy‑storage or wind‑power project.