GFHVT1500‑A‑59E 1500Vdc Fast‑Acting Fuse 100‑400A
GFHVT1500‑A‑59E flush‑end DC fuse,1500Vdc,100‑400A,aR 250kA interrupt. UL/IEC compliant for BESS & battery‑pack protection. Download datasheet
20+ Years Experience
Over 20 years in electrical protection and fuse manufacturing.
Strict Quality Control
Rigorous testing ensures reliable product performance.
Get a Quote
GFHVT1500‑A‑59E Series 1500Vdc Fast‑Acting Flush‑End Square‑Body Fuse 100‑400A
SKU Series:GFHVT1500‑A‑59E|Fuse Class:aR|Voltage:1500V DC|Current Range:100‑400A|Max Interrupt:250kA@1500Vdc|Terminal: Flush‑end contact
Product Overview
The GFHVT1500‑A‑59E series is compact square‑body fast‑acting aR fuse link with flush‑end contact terminals, purpose‑built for high‑energy DC circuits. Rated for 1500Vdc, current range 100A‑400A, maximum interrupting capacity 250kA@1500Vdc, minimum breaking current ≥5×In.
This flush‑end contact design optimizes space‑saving cabinet layout, suitable for compact energy‑storage racks and battery‑module internal protection. It delivers outstanding DC fault‑clearing performance, low watt‑loss, high cycling endurance and ≥20g shock‑vibration resistance. Two‑pcs M10 mounting holes for reliable busbar assembly.
Key Features & Benefits
- ✅ Flush‑end contact terminal design, space‑saving for compact cabinet / rack layout
- ✅ Rated voltage 1500V DC, reduce conductor cost and improve overall system efficiency
- ✅ Fast‑acting aR semiconductor‑protection characteristic, time constant ≤5 ms
- ✅ High interrupt rating: 250 kA @1500Vdc, minimum breaking current ≥5In
- ✅ Low power loss, superior charge‑discharge cycling capability
- ✅ Excellent mechanical shock & vibration resistance (≥20g)
- ✅ 2 pcs M10 mounting holes for flush‑end busbar connection
- ✅ RoHS compliant, REACH statement available upon request
- ✅ Complies with UL 248.1 / UL 248.13, IEC 60269‑1 / IEC 60269‑4
Main Electrical Specifications
| Parameter | Specification |
|---|---|
| Rated Voltage | 1500 Vdc |
| Rated Current Range | 100A‑400A |
| Fuse Class | aR Fast‑acting |
| Max Interrupt Capacity | 250 kA @1500Vdc |
| Minimum Breaking Current | ≥5×In |
| Time Constant | ≤5 ms |
| Terminal Type | Flush‑end contact (M10 mounting holes) |
| Storage Temperature | -40 ℃ ~ +120 ℃ |
| Normal Operating Ambient | -5 ℃ ~ +40 ℃ |
| Allowable Operating Temperature | -40 ℃ ~ +85 ℃ |
Note: Recommended continuous operating current ≤75 % of fuse nominal rating under standard ambient‑temperature conditions.
Part Numbering Explanation
Example Model: GFHVT1500‑400A‑59E
| Code | Definition |
|---|---|
| GF | Manufacturer Code (GFEV) |
| HV | High‑Speed / Fast‑Acting |
| T | Ceramics Body |
| 1500 | Rated Voltage:1500Vdc |
| 400 | Rated Current(A) |
| A | Terminal: Flush‑end contact |
| 59E | Series Code |
Mechanical Dimensions & Installation
Flush‑end contact terminal with two M10 mounting holes, compact square housing for narrow‑space rack installation.
Installation note: M10 screw hole; max hole depth 11.5 mm, minimum thread length 9.5 mm. Apply proper tightening torque to avoid over‑heating contact points.
Full Part List Table
| Part Number | Fuse Amps | Melting A²s | Clearing A²s | Power Loss 80%In(W) | Power Loss 100%In(W) | RoHS | REACH |
|---|---|---|---|---|---|---|---|
| GFHVT1500‑100A‑59E | 100A | 3085 | 8568 | 43 | 55 | ● | ● |
| GFHVT1500‑125A‑59E | 125A | 4746 | 13182 | 47 | 60 | ● | ● |
| GFHVT1500‑160A‑59E | 160A | 7415 | 20597 | 53 | 68 | ● | ● |
| GFHVT1500‑200A‑59E | 200A | 11547 | 31208 | 69 | 86 | ● | ● |
| GFHVT1500‑250A‑59E | 250A | 18720 | 50594 | 86 | 108 | ● | ● |
| GFHVT1500‑315A‑59E | 315A | 31897 | 86207 | 102 | 128 | ● | ● |
| GFHVT1500‑350A‑59E | 350A | 42423 | 114556 | 110 | 137 | ● | ● |
| GFHVT1500‑400A‑59E | 400A | 61039 | 164970 | 122 | 153 | ● | ● |
Application Fields
- ⚡ Compact Battery‑Energy‑Storage System(BESS) main‑circuit short‑circuit protection
- ⚡ Lithium‑ion battery‑module internal short‑circuit protection
- ⚡ Backup short‑circuit protection for DC relays & DC contactors
- ⚡ Narrow‑space energy‑storage rack / cabinet DC busbar protection
- ⚡ Maintenance safety disconnector / DC isolation for industrial DC equipment
Standards & Certifications
| Standard / Certificate | Status |
|---|---|
| UL 248.1, UL 248.13 | Complied |
| IEC 60269‑1, IEC 60269‑4 | Complied |
| RoHS | Compliant |
| REACH | Declaration available upon request |
Operating & Derating Conditions
Important: Recommended continuous operating current ≤75 % of fuse nominal rating under standard conditions.
Ambient Temperature Derating
Above 40 ℃ ambient temperature requires rated‑current derating according to derating curve. Below ‑5 ℃, pre‑arcing time for low overload will slightly extend.
Altitude Derating
Normal working altitude ≤2000 m. For closed‑enclosure applications at altitude 2000‑4500 m: derate rated current 2‑5 % per 1000 m elevation increase. Air insulation strength drops at high altitude, check clearance per GB/T 16935.1.
Forced Air Cooling Correction
Forced ventilation improves heat‑dissipation and raises allowable continuous operating current, refer to Kv correction curve vs wind‑speed(m/s).
Time‑Current Characteristic Curve
Covers rating 100‑400A. Curve tolerance: ±15 % on current axis. Minimum breaking current =5 × In.
Frequently Asked Questions
1: What is the minimum breaking current for GFHVT1500‑A‑59E series?
1: Minimum breaking current equals 5 times nominal rated current(5In).
2: What does flush‑end‑contact terminal mean?
2: Flush‑end contact (Type‑A) is flat end‑face mounting with two M10 holes, designed for compact rack installation to save cabinet internal space.
3: Can GFHVT1500‑A‑59E be used for lithium‑ion battery‑module protection?
3: Yes. It is aR‑class fast‑acting flush‑end fuse for battery‑module and compact‑BESS DC‑circuit protection. Please verify I²t coordination with your BMS.
4: What derating shall I apply for sealed cabinet working at high altitude?
4: For sealed cabinets operating above 2000 m altitude, derate 2‑5 % per 1000 m elevation. Higher derating ratio applies for larger‑ampacity models.
5: What is suggested maximum continuous operating current?
5: Under standard ambient‑temperature conditions, continuous working current should not exceed 75 % of fuse nominal rated‑current.
Download Datasheet & Resources
📄 Download GFHVT1500‑A‑59E Series Datasheet(PDF) GFHVT1500-A-59E-Series.-100-400A-1500Vdc-fast-acting fuse
📎 Request REACH Declaration | Request CAD Drawing | Ask Technical Support
Need fuse‑selection support? Contact our engineering team for I²t‑matching and system‑coordination advice for your compact‑energy‑storage project.